MajorTPS 24/48 VDC Telecom Power Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1 Product List | Order | Contact Us
MajorTPS 24/48 VDC Telecom Power Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1
Search:  
 
MajorPower.Com: MajorTPS Telecom Power Systems 24/48 VDC Communication Rectifier Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1 MajorPower.Com: MajorTPS Telecom Power Systems 24/48 VDC Communication Rectifier Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1 MajorPower.Com: MajorTPS Telecom Power Systems 24/48 VDC Communication Rectifier Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1 Tel: 514.369.4919 Fax: 514.369.4817

  Home > Telecom Index > MajorTPS Systems

Email this page MajorTPS 24/48 VDC Telecom Power Systems with Distribution LVD, 7, 12, 15, 25, 60, 100, 200 Amps, N+1
MajorTPS Telecom Power Systems 1U

 

MajorTPS Telecom Power Systems are full featured, communication power systems consisting of redundant rectifiers, distribution, and battery low voltage disconnect, in a compact rackmount enclosure.

MajorTPS Systems are ideal for environments where space is limited and full telecom quality is required.

MajorTPS Telecom Power Systems

MajorTPS Telecom Power Systems Features
  • System Capacities
    • 24 Volts DC - 10 Amps & 20 Amps
    • 48 Volts DC - 7, 12, 14, 24 Amps
  • Complete package
    • Parallel rectifiers, DC distribution & LVD.
  • Compact
    • Largest system is only 1RU, mounts in 19" or 23" rack.
  • Flexible
    • Designed to operate with or without batteries.
  • High reliability
    • Parallel redundant plug-in rectifiers, seperate AC input.
  • Integrated Output Distribution
    • 6 alarmed GMT fuses
  • Metering & Status
    • LED status indicators
  • Warranty
    • Comprehensive 24 month
MajorTPS Telecom Power Systems

MajorTPS 1U Brochure Download MajorTPS Telecom Power Systems Pricing & Order
  MajorTPS 1U Brochure Download MajorTPS System 1U Specs   MajorTPS10/24SYS
  MajorTPS20/24SYS
MajorTPS7/48SYS
MajorTPS12/48SYS
MajorTPS15/48SYS
MajorTPS25/48SYS

MajorTPS Telecom Power Systems Model Selection Guide
Systems 24 VDC Systems 48 VDC Systems
Model MajorTPS
10/24SYS
MajorTPS
20/24SYS
MajorTPS
7/48SYS
MajorTPS
12/48SYS
MajorTPS
15/48SYS
MajorTPS
25/48SYS
Input
Voltage 120/220 VAC 220 VAC 120/220 VAC 220 VAC
Current
(max per rectifier)
5.2A @ 120V
2.8A @ 220V
4.8A @ 220V 5.2A @ 120V
2.8A @ 220V
4.8A @ 220V
Protection Each rectifier seperately fused
Frequency 47 - 63 Hz
AC Connections 120 VAC: 6' line cord, (5) 15R receptacle
220 VAC: Bare End
Output
Voltage 24 VDC 48 VDC
Current
(max per rectifier)
10 Amps 20 Amps 7 Amps 12 Amps 14 Amps 24 Amps
Number of Rectifiers 1 2 1 1 2 2
Protection Each rectifier seperately fused
Connections 6 position terminal block suitable for #22 - #12 AWG
Load Connection Terminal Block- seperate
Return Connection Removable terminal block- line and return
Alarm
Local LEDS-Rectifier Fail, Fuse Fail
Remote Form 'C'contacts-Rectifier 2 Fail, Fuse Fail
Connection Molex Connector with 6' battery cable included
Protection External fuse or circuit breaker
Low Volts Disconnect Internal - 30A maximum
Temp Compensation 2 step - sensor optional
Rectifiers
Configuration (Parallel Redundant Slide-in Rectifiers) (2) 7 Amp or 10 Amp (2) 10 Amp (2) 7 Amp or 10 Amp (2) 10 Amp
Controls ON/OFF Switch, Volts, Adjust pot
Alarms Green LED - "ON" / Red LED - "FAIL"
Protection Input and output fuses
Distribution
Configuration 6 position, 6-10A GMT fuses
Alarms Red LED - "Fuse Fail"
Low Voltage Disconnect
Contactor 30 Amps
Drop-Out Factory Set to 1.75 VPC
Remote Alarms
Form "C" Contacts Rectifier 1 Fail; Rectifier 2 Fail; Fuse Fail
Mechanical
Dimensions 17"W x 14"D x 2"H
Weight 15lbs 20 lbs 15lbs 15lbs 10 lbs 22 lbs
Cooling Fan Cooled - requires 1RU above
Mounting Suitable for 19" or 23" rackmount
Battery System
Connection Amp commercial MATE-N-LOK
Protection Battery Fuse
Battery System (Options)
Temp Compensation Remote Sensor with 6' cable

Optional Battery Pack
Model 24v runtime (Minutes) Model -48 runtime (Minutes)
4A 6A 8A 10A 2A 3A 4A 5A 7A
BP3 180 120 90 60 BP1 240 140 120 60 45
BP4 360 240 180 120 BP2 480 280 240 120 90

 
Custom Applications - Contact MajorPower.Com
 
Visa MasterCard American Express Accepted MajorTPS Telecom Power Plants       Email This Page | Print Page | Terms & Conditions | About MajorPower.Com | Home
MajorTPS Telecom Power Plants sales@majorpower.com
copyright 2002 MajorTPS Telecom Power Plants