| Input |
| Input Voltage |
176 VAC - 275 VAC, single phase
(275 VAC - 300 VAC, no damage
121 VAC - 175 VAC: Derated to 70% Load,
90 VAC - 120 VAC: Derated to 50% Load)
|
| Input Current |
<4 Amps (Low Line Input. Full-Load) |
| Line Frequency |
45 - 65 Hz |
| Power Factor |
>0.99 (Nominal Input, Full-Load) |
| THD |
Typical 5% (Nominal Input, Full-Load) |
| Efficiency |
>90% (Typical 91%) Nominal Input. Full-Load |
| Inrush Current |
<9 Amps (peak), Nominal Input, Full-Load, Cold Start |
| Start Time Delay (Walk-in) |
3 - 10 Seconds |
| Protection |
Fuse |
| Output |
| DC Output Voltage |
40 - 60 VDC |
| Output Power |
600 Watts (Maximum) |
| Regulation |
Load: <±0.5% (Load 0 - 100%); Line: <±0.1% (Load 0 - 100%) |
| Current Limit |
<110% of rated Output Current |
| Noise |
Audio Band: <2mV (-48 VDC), CCITT
Wide Band: <10mVrms (10 Khz - 100 MHz)
Acoustic: <55dBA @ 1M |
| Current Sharing |
<5% of Rated Output Current |
| Dynamic Response |
10 - 90% Load Change; Overshoot <5% Rated Output Voltage
Recovery Time <1 ms to <± 1% Rated Output Voltage |
| Protection |
Fuse |
| Protection |
| AC Input Voltage High |
Automatic Shutdown and Recovery (300 V ± 10 V) |
| AC Input Voltage Low |
Automatic Shutdown and Recovery (80 V ± 10 V) |
| Brown-Out |
No Damage During Brown Out Conditions |
| Output Short |
Automatic Shutdown and Recovery (170% - 200% of Rated Current) |
| Output Current |
Automatic Shutdown and Recovery |
| High Voltage Shutdown |
If rectifier module voltage exceeds preset value, module will shut down and latch |
| Over Temperature |
Automatic Shutdown and Recovery (100 ±5°C) |
| Environmental |
| EMI/RFI Suppression |
EN 55022, BS 6527 Class B, FCC Part 15 Subpart J & CISPR 22 Class B |
| Current Harmonic |
EN 61000-3-2/A12, EN 60555-2, IEC 555-2 Class A |
| Voltage Fluctuation |
EN 61000-3-3, EN 60555-3 |
| Electrostatic Discharge |
EN 61000-4-2, IEC 1000-4-2,
IEC 801-2 Level 4,15KV Air Discharge, 8KV Constant Discharge |
| Radiated Susceptibility |
IEC 1000-4-3, IEC 801-3 Level 3, 10V/m |
| Electrical Fast Transients |
EN 61000-4-4, IEC 1000-4-4, IEC 801-4 Level 4, 4KV |
| Conducted Susceptibility |
IEC 1000-4-6 Level 3, 10V/m |
| Lightning/Surge |
ANSI/IEEE C62.41-1, 1991 B3, IEC 1000-4-5 Level Special (6KV) |
| Status/Alarm Indicators |
| AC ON |
Green LED |
| Rectifier Failure Alarm (RFA) |
Red LED |
| Current Limit (CL) |
Amber LED |
| Adjustments |
| Current Limit (CL) |
Setting from System Controller (SMR or CSU) |
| Float Voltage (FLO) |
Setting from System Controller (SMR or CSU) |
| Test Points (I+,I-) |
Output Current Test |
| Remote Control |
Emergency Shut Down, Float / Equalize Mode, Current Limit |
| Physical |
| Dimensions |
2.5"W x 5.2"H x 9.57"D (63.6 x 132 x 243.1mm) |
| Weight |
4.4 lbs / 2.0 kg |
| Cooling |
Fan Cooling (>5 Years Long Life) |
| Heat Dissipation |
228BTU/Hour Max Per Module |
| Approvals |
| Safety |
Meets IEC 950, EN 60950, UL/cUL/TUV/CE Approval |
| MTBF |
>150K Hours at 25°C / 47°F Environment Temperature |