| Electrical
Input |
| Nominal Voltage |
120 or 230 VAC (see Model
Selection Guide) |
| Power ratings |
700-2000 VA |
| Input Voltage Range |
80-144 VAC (without using batteries) |
| Input Power Factor |
>.95%, typical |
| Operating Frequency |
50/60 Hz, Auto-sensing |
| Frequency Range |
45 - 65 Hz, auto-sensing |
| Input Protection |
Fuse or circuit breaker |
| Electrical
Output |
| On Utility Voltage Regulation |
±3% of nominal |
| On Battery Voltage Regulation |
±3% of nominal |
| Load Crest Factor |
3 to 1 ratio |
| Nominal Output Voltage |
Same as selected input voltage |
| Output protection |
Electronic overload sensing,and circuit
breaker protection |
| Efficiency |
89 - 92%, depending on load |
| Battery |
| Internal Battery type |
Sealed, lead-acid; maintenance free
700/1000VA:(2)12V, 9Ah
1250/2000VA:(4)12V, 9Ah |
| EBM Battery Type |
PW9125 24 EBM:(8)12v, 9Ah; PW9125
48 EBM:(8)12v, 9Ah |
| On Battery Runtime |
See Battery
Runtimes |
| Battery Replacement |
Hot-swappable internal and external
batteries |
| Recharge Time |
<2 hours from complete discharge
to 90% capacity at nominal line conditions |
| Start-On-Battery |
Allows start of UPS without utility
input |
| Communications |
| Audible Alarms |
UPS alarm conditions,including: On-Battery,Low
Battery,Overload, UPS Fault |
| Serial Port |
RS-232 Port standard |
| ConnectUPS-M SNMP Module
(Optional) |
SNMP Card adds direct control
and monitoring capabilities in SNMP-based networks. |
| Communications cable |
6-foot communications cable
included |
| USB Module
(Optional) |
Allows start of UPS to
communicate with Windows 98 computers vbia USB port; factory-installed
option only |
| General |
| Topology |
True online, double-conversion |
| Diagnostics |
Full system self-test on power up |
| UPS Bypass |
Automatic on Overload or UPS failure
<4ms |
| Dimensions and Weights |
See Model
Selection Guide |
| Environmental
and Safety |
| Safety Markings |
UL, CSA, and NOM |
| EMC Markings |
FCC Class B and VCCI Class II |
| Operating Temperature |
0 to 40 C (32 to 104 F) |
| Storage Temperature |
0o to 25o
C (32o to 77o F) |
| Relative Humidity |
5%to 95% non-condensing |
| Surge Supression |
IEEE/ANSI C62.41 Category B (formerly
587) |
| Network Transient
Protector |
In & out jack for telephone/modem
protection of 10Base-T network cable;
UL497A tested. |
| Audible Noise
at 1 meter |
700-1000VA: <45dB
(on utility); <50dB (on battery) |
| REPO ports |
Meets NEC code 645-II intent and UL
requirements |