| Electrical
Input |
| Nominal Voltage |
For user-selectable voltages see Model
Selection Guide |
| Input Voltage Range |
80-144 VAC(120/140/160-276 VAC i Models) |
| Input Power Factor |
>.95% |
| Operating Frequency |
50/60 Hz, Auto-sensing |
| Frequency Range |
45 - 65 Hz |
| Input Protection |
Fuse or circuit breaker |
| Electrical
Output |
| On Utility Voltage Regulation |
+/-2% of nominal |
| On Battery Voltage Regulation |
+/-3% of nominal |
| Nominal Output Voltage |
Same as selected input voltage |
| Output Voltage Waveform |
Sine Wave |
| Output Voltage Distortion |
<3%THD |
| Output protection |
Electronic overload sensing,and circuit breaker
protection |
| Efficiency |
Online Mode:>86%; Hi-Efficiency Mode:>90% |
| Battery |
| Internal Battery type |
Sealed, lead-acid; maintenance free |
| EBM Battery Type |
Sealed, lead-acid; maintenance free |
| On Battery Runtime |
See Battery
Runtimes |
| Battery Replacement |
Hot-swappable internal and external batteries |
| Recharge Time |
<4 hours to 90%capacity |
| Start-On-Battery |
Allows start of UPS without utility input |
| Communications |
| User Interface |
LCD status screen |
| Audible Alarms |
UPS alarm conditions,including: On-Battery, Low
Battery, Overload, UPS Fault |
| Network transient Protector |
In and out jack for all models. UL497A tested |
| REPO Port |
Meets NEC code 645-11 intent and UL requirements |
| Communications |
One RS232 Serial Port;One Communications Slot;
One USB Port |
| Communications cable |
6-foot communications cable included |
| Power Management Software |
Powerware Software Suite CD, free
updates on |
| General |
| Topology |
True online, double-conversion |
| Diagnostics |
Full system self-test on power up |
| UPS Bypass |
Automatic on Overload or UPS failure <4ms |
| Transfer Time to battery |
0 ms |
| Dimensions and Weights |
See Model Selection Guide |
| Overload Capacity |
125% for 10 minutes before transfer to bypass;
150% for 10 seconds before transfer to bypass |
| Environmental
and Safety |
| Safety Certifications |
UL1778;cUL22.2 NO.107.1 (CE Marked. EN 50091-1-1
AND IEC 60 950) |
| EMI Compliance |
FCC Part 15, Class B (700-1500), Class A (2000-3000)
230V,
EN 50091-2 Class B (700-1500), Class A (2000-3000) |
| Operating Temperature |
0 to 40 C (32 to 104 F) |
| Storage Temperature |
-15 to 50 C (5 to 122 F) |
| Storage Temperature |
0o to 25o C (32o
to 77o F) |
| Relative Humidity |
0%to 95%non-condensing |
| Immunity |
EEE C62.41, IEC 61000-4 -2, -3, -4, -5 |
| Network Transient Protector |
UL497A |
| Audible Noise at 1 meter |
700-1000VA: <45dB;1500VA <50dB;
2000-3000 <52dB |
| Altitude |
3000m (10,000 ft) without deteriorating |
| Note: Due to continuing product
improvement programs, specifications are subject to change without