| Electrical
Input |
1000 - 2200 VA |
2400 -3000 VA |
| Nominal Voltage |
120/208/230;
For user-selectable voltages see
Model Selection Guide |
120/208/230/240;
For user-selectable voltages see
Model Selection Guide |
| Input Voltage Range |
Low
voltage: 77-152V; High voltage:
154-288V |
| Operating Frequency |
60/50 Hz, Auto-sensing |
| Frequency Range |
45 - 65 Hz |
| Electrical
Output |
| On Utility Voltage Regulation |
-10% to +6% of nominal |
| On Battery Voltage Regulation |
±5% RMS |
| Voltage Wave Shape on Battery |
Sine Wave |
| Output protection |
Short-circuit protection |
| Battery |
| Battery type |
Sealed, lead-acid; maintenance-free |
| Battery Runtime |
See Battery
Runtimes |
| Battery Replacement |
Hot-swappable internal
batteries and external batteries modules |
| Recharge Time |
<3 hours to 90%
usable capacity |
| Start-On-Battery |
Allows start of UPS
without utility input |
| Communications |
| User Interface |
Front Control Panel |
| Audible Alarms |
For various UPS alarm
conditions including:
On Battery, Low Battery, Overload, and UPS fault |
| Network transient Protector |
UL 497 A, In/Out jacks
RJ45 (high voltage models network protection) &
RJ11 (low voltage models modem protection) |
| REPO Port |
Meets NEC code 645-11
intent and UL requirements |
| X-Slot Interface |
RS232 Single Serial
Module standard; Other options available: RS-232 Multi-Port Module
(6), SNMP/Web Module; USB Module; Relay Module |
| Cable |
6-foot
communications cable included |
| Power Management Software |
Powerware
Software Suite CD, free updates on |
| General |
| Diagnostics |
Full system self-test
on power up |
| UPS Bypass |
No Bypass |
Internal Bypass |
| Transfer Time to battery |
2-4ms typical |
| Dimensions and Weights |
See Model
Selection Guide |
| Overload Capacity |
110% overload, shut down after
3 minutes. 150% overload, shut down 10 cycles. |
110% overload for 30 seconds short-circuit
protected. |
| Environmental
and Safety |
| Safety Certifications |
1UL; cUL; NOM; CTick;
CE Mark |
| EMI Compliance |
FCC Part 15, EN50091-2, Class A
for 2.2kVA and RM; CLass B for 1 and 1.5kVA tower models |
FCC Part 15, EN50091-2, Class A |
| Operating Temperature |
0 to 40° C (32 to
104° F) |
| Storage Temperature |
-15 to 50°
C (5 to 122° F) |
| Relative Humidity |
0% to 95% non-condensing |
| Lightning & Surge Protection |
ANSI/IEEE C62.41, IEEE
587, TEC61000-4-5 |
| Surge Energy Rating |
480 Joules |
| Audible Noise |
Less
than 40dBA typical |
| Altitude |
3000m (10,000 ft) without
derating |
| Note: Due to continuing product
improvement programs, specifications are subject to change without
notice. |