| Performance |
| Input |
85-135 / 170-270 VAC (selectable),
47-63 Hz |
| Power Factor |
0.7 |
| Regulation |
±1% at direct output; ±2%
through "oring" diode |
| Ripple |
1% |
| Efficiency |
80-85% @ full load |
| Front Panel Output Voltage Adjustment
Pot Range |
10% |
| Protection |
- Output fuse for reverse polarity
- Current limit and fold back
- Input circuit breaker on rectifier module front panel
- Automatic high temp output power reduction starting @ 50°C
ambient and full load
- Forced air cooling with filter provided
|
| Mechanical |
| Front Panel |
Anodized aluminum |
| Base And Cover |
Vinyl laminated aluminum |
| Mounting |
Rack (19" or 23" - 2 RU) or bulkhead mounting optional |
| 560 Watt models |
IEC AC entry module;
6' power cord with MENA 5-15 plug, 115 VA;
¼" - 20 Output stud
|
| 1000 Watt models |
6' power cord, hard-wired with NEMA 6-15 plug, 230 VAC
Output bus bar
|
| LED |
Output "OK" |
| Alarms |
Loss-of-output alarm contact - Form 'C |
| Test Points |
Front panel voltage |
| Temperature Rating |
-40°C to +60°C; Derate linearly from 100% laod @ 50°C
to 75% @ 60 |
| Protection |
Output fuse for reverse polarity,
Current limit and fold back,
Input circuit breaker on rectifier module front panel,
Automatic high temp output power reduction starting @ 50°C
ambient and full load,
Forced air cooling with filter provided
|
| Compliance |
UI 1950, EN 50082, EN 55014 |
| Options |
- Three stage charger function with gel / lead-acid selector (replaes
voltage adjustment pot) Model: CFB
- Temperature compensation (for battery charging) Models: TCS-12/24,
TCS-48
- Battery equalize (timer required) Model: BEQ
- DC quick connect kit Models: QCK-3 (for 2-3 unit PM system)
QCK-6 (for 4-6 unit PM system)
- "Universal" mounting bracket; Model: UMB-PM
|