| Input |
| Standard Voltage |
110, 120, 208, 220,
240, 380, 400, 480, 550, 575, and 600 VAC |
| Phases |
1 and 3 phase |
| Frequency |
50Hz or 60Hz |
| Power Factor |
0.75 (1 phase), 0.85 (3
phase) at full load when tested on battery and resistive load |
| Efficiency at Full Load |
Typical 87% (1 phase),
90% (3 phase) |
| Output |
| Standard Nominal Voltage |
12, 24, 36, 48, 72, 125,
250, 380, 480 and 600 VDC |
| Power |
From 60W to 180kW Standard |
| AC Ripple
Voltage |
Standard:
Single phase: 10% RMS on battery; 3-Phase: 3% RMS on battery; Unfiltered, commercial grade, NON NEMA/PE5 Compliant |
F
Option: 12/24/48 Volt: 1% on resistive load (PE5 filtered off battery);
30 mV on batteries (PE5: Filtered on battery)
125/240 Volt: 2% on resistive load (PE5 filtered off battery);
100 mV on batteries (PE5: Filtered on battery)
|
T
Option: 12/24/48 Volt: 30 mV on resistive load
125 Volt: 100 mV on resistive load
240 Volt: 200 mV on resistive load
|
| Static Regulation |
< 0.5%
for simultaneous variations of +10/-12% input voltage,
±5% input frequency and 0-100% load |
| Dynamic Regulation |
±6% from 10%-90%
and 90%-10% load variation (t<300msec) |
| Parallel Operation |
Random:
Similar chargers can be operated in random Parallel |
EMC
(CE Marked Units Only) |
Conducted
(150kHz-30MHz) and radiated (30MHz-1GHz): en55011 class A |
| Electrostatic
discharge: EN61000-4-2 level 2/3 (4kV contact, 8kV air) |
| Radiated
susceptibility: EN61000-4-3 level 3 annex D (80MHz-1GHz @ 10V/m) |
| Electrical
fast transient: EN61000-4-4 level 3 (2kV) |
| Surge
immunity: EN61000-4-5 level 3 (1kV l/l, 2kV L/GND) |
| Conducted
susceptibility: EN61000-4-6 level 3 (150kHz to 80MHz, 10v) |
| Voltage
interrupt: EN61000-4-11 (30, 60 & 90%-10-10 & 500ms) |
| Protection |
| Over-Current |
Soft start |
| Automatic current limiting
curcuit, adjustable from 20% to 120% of nominal rating |
| Input thermal-magnetic
circuit breaker and DC output fuse standard |
| Voltage Transients |
Surge suppression on input
and output reverse polarity |
| Mechanical and Physical |
| Enclosure |
CEMA/NEMA1(IP20), 14GA (2mm) steel
C/W hinged front access door |
| Finish |
Phosphatised and primed
prior to painting with ASA61, light gray |
| Natural convection colling
up to 130A output current |
| Cooling |
Forced air cooling assitance for units
over 130A output current
(N.B. Floor mounted models are proveded with 3in. (75mm) clearance
at bottom to facilitate handling by lift truck, pallet truck or slings) |
| Environmental |
| Audible Noise |
45 to 65 dBa at 3ft (1
meter) rating dependant |
| Operating Temp. Range |
32°F to +122°F
(0°C to 50°C)/Storage -40°F to 185°F (-40°C
to 85°C) |
| Temperature De-Rating |
0.83%/°F from 122°F
to 140°F (1.5%/°C from 50°C to 60°C) |
| Operating Humidity |
Up to 95% (non condensing) |
| Altitude De-Rating |
0% for 1st 3300ft (1000m),
7% per 3300ft (1000m) over 3300ft (1000m) |