| Input Voltage
|
24, 36, 48, 125, 250
VDC ±20% are standard. Other inputs available. |
| Input Protection
|
Thermal fuse, Inrush
current limiting and Reverse polarity protection. |
| Input
Isolation |
Input-chassis:
500VDC @ <60V, 1500VDC @ >60V Input-output
/ Output-chassis: 2250VDC. |
| Output
Voltage |
120/208 VAC/60 Hz; (230/400 VAC/ 50 Hz and 115/200 VAC/400 Hz Available.)
Continuous output with grounded neutral. Isolated floating output available. |
| Efficiency
|
Minimum 78% at full
load |
| Line Regulation |
Maximum 0.5% |
| Load Regulation |
Maximum ±6% from 10%
load to full load |
| Output Protection
|
Current limiting with
short circuit protection.
Thermal shutdown with automatic reset in case of
insufficient airflow. |
| RFI Suppression
|
Meets requirements
of EN 55022: 1987 Class B conducted emissions |
| Crest
Factor |
Maximum 3
at 90% load |
| Harmonics (THD)
|
Less than 5% at full
load |
| Operating Temp.
|
0°C to +50°C
(internal fan) |
| Temp.
Drift |
0.05% per
°C over operating temperature range |
| Dimensions
|
5.3"H x 7.5"W
x 15.5"L (3U Rackmount ears included) |
| Connections
|
Input: Compression-type
terminal. Output: Standard AC Receptacle. |
| Weight |
13 pounds (5.9Kg) |
| Warranty |
Twelve months subject
to client application within accepted engineering
practice.
Designed to meet common approval requirements. |