Input
|
MajorFDP24/150
|
MajorFDP48/150 |
|
Voltage |
24 VDC |
48 VDC |
| Current |
Max 75 Amps oer side in an A & B configuration |
| Circuits |
10 outputs per side, each with a seperate fuse |
| Connections |
A & B sides: mechanical lugs for (2) #6 conductors
Return: return bus with lugs for (2) #6 conductors
|
|
Output
|
|
|
Voltage |
24 VDC |
48 VDC |
|
Current |
Max 75 Amps per side in an A & B configuration |
| Number of Circuits |
10 outputs per side, each with a separate fuse |
| Maximum Circuit Size |
15 Amps |
| Connections |
Load: 20 position terminal block suitable for #10 - 16 fork lugs
Return: common return bus with 20 lugs for #4 - 16 wire |
| Protection |
GMT fuses, 15 Amps maximum |
| Metering
& Alarms |
|
| Meters |
3 digit LCD voltmeter |
| Alarms |
"Fuse Fail" red LED |
| Remote |
Form "C" contact for "Fuse Fail" |
| Connection |
Terminal block for #14 -22 stranded wire |
|
Monitoring
|
|
|
Breaker/Fuse Trip Alarm |
LED |
| Remote Alarm Contact |
Form 'C' |
| Connection Type |
Compression |
| Digital Voltmeter |
Yes
|
|
Physical
|
|
|
Rack Units |
1 RU |
| Rack Mounting |
19" or 23" |
| Mounting Style |
Flush, 2" or 4" |
| Cabinet |
Painted C-147 semi-gloss textured blue with anodized aluminum faceplate |
| Dimensions |
17"W x 12"D x 1.75" H
|
| Weight |
8 lbs |